14 | Unit installation
Installer and user reference guide
65
SV1A25AJV1B+SV4~8A14AJV1B
VRV 5 safety valve unit
4P749917-1 – 2023.09
b Indoor unit
c Sound insulation (field supply)
▪ Drainage. Make sure condensation water can be evacuated properly.
▪ Drain pipe length. Keep drain piping as short as possible.
▪ Drain pipe size. Keep the pipe size equal to or greater than that of the
connecting pipe (vinyl pipe of 20 mm nominal diameter and 26 mm outer
diameter).
▪ Bad odours. To prevent bad odours and air going into the unit through the drain
piping, install a trap.
a Trap
▪ Ammonia. Do not connect the drain piping directly to sewage pipes that smell of
ammonia. The ammonia in the sewage pipe might enter the unit through the
drain piping and cause corrosion.
▪ Combining drain pipes. It is possible to combine drain pipes. Use drain pipes and
T-joints with the correct gauge for the operating capacity of the units.
a T-joint
▪ Spacing. Respect the following requirements:
a
[mm]
c
≥
485
c
≥
485
d
≥
500
b
≥
720
(≥49.5)
291
f: 875 f: 450
A≥1800≥100
a
≥5
e e
g
e
[mm]
A Minimum distance to the floor
a Switch box