14 | Unit installation
Installer and user reference guide
76
SV1A25AJV1B+SV4~8A14AJV1B
VRV 5 safety valve unit
4P749917-1 – 2023.09
2
1
b
a
a
a
a
c
PH2
SW8
a Screw
b Damper
c Damper wire
To remove the duct connection
1 Remove the four screws.
2 Store the screws in a safe place.
3 Pull the duct connection from the unit.
PH2
SW8
To install the duct connection
1 Position the duct connection onto the other side of the unit.
2 Attach the duct connection with four screws.
PH2
SW8
3.2 N•m
To install the damper
1 Install the damper on the other side of the unit:
Carefully guide the wires from the outside to the inside through the small
hole in the unit's metal plate. Take care not to damage the connector and
the earth wire connection.
Position the damper onto the unit. Take care not to pinch and damage the
wires between the damper and the unit.
Pull the wires through until the foam insulation fits properly in the small hole
in the unit's metal plate. This makes the connection airtight.
Attach the damper with four screws.