VI.KT.G6.02 © Danfoss | 2016.05 | 13
Maintenance
Displace (parallel displacement) 2176
Setting range Factory setting
-20 ... 20 0
Adjust the parallel displacement of the heat curve with a number of degrees, if required.
Whether it is reasonable to change the ‘Slope’ (at outdoor temperatures below 0 °C) or
parallel displacement (at outdoor temperatures above 0 °C) will depend on the individual
heat requirement.
Small increases or reductions in the heating temperature can be implemented by means of
the parallel displacement.
Temp. min. (ow temp. limit, min.) 2177
Setting range Factory setting
10 ... 150 °C 10 °C
Choose the allowed min. ow temperature for your system. Adjust the factory setting, if
required.
Temp. max. (ow temp. limit, max.) 2178
Setting range Factory setting
10 ... 150 °C 90 °C
Choose the allowed max. ow temperature for your system. Adjust the factory setting, if
required.
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.