VI.KT.G6.02
10 | © Danfoss | 2016.05
Maintenance
2 sec.
Enter the maintenance menus.
Date - time 1000
It is only necessary to set the correct date and time in connection with the rst use of the
ECL Comfort 110 controller or after a power break of more than 36 hours (see the chapter
on Adapting the ECL Comfort 110 controller).
Flow temp. (ow temperature control) 2000
Heat curve
The ECL Comfort 110 controls the heating system according to the calculated ow
temperature under the inuence of the return and / or room temperature.
The desired ow temperature is dened by 5 settings: ‘Temp. max., ‘Temp. min., ‘Slope’,
‘Displace’, and ‘Knee point.
Desired ow temperature
-20 -10 0 10 20-30
20
30
40
50
60
70
80
90
100
110
10
[°C]
[°C]
Heat curve
Slope’
Temp. max.
‘Displace’
‘Knee point
Temp. min.’
Outdoor temp.
The calculated ow temperature can be inuenced by connected sensors, ‘Boost’ and ‘Ramp
etc.