VI.KT.G6.02
16 | © Danfoss | 2016.05
Maintenance
This limitation is based on a PI regulation where P (Gain) responds quickly to deviations
and I (Intgr. time) responds slower and over time removes the small osets between the
desired and actual values. This is done by changing the desired ow temperature.
Intgr. time (time constant for room temp.) 3015
Setting range Factory setting
OFF / 1 ... 50 OFF
Controls how fast the room temperature adapts to the desired room temperature (I control).
OFF: The control function is not inuenced by the ‘Intgr. time’.
1: The desired temperature is adapted quickly.
50: The desired temperature is adapted slowly.
Gain - max. (room temp. limitation, max.) 3182
Setting range Factory setting
-9.9 ... 0.0 -4.0
Determines how much the ow temperature will be inuenced (decreased) if the room temperature is
higher than the desired room temperature (P control).
-9.9: The room temperature has a big inuence.
0.0: The room temperature has no inuence.
Gain - min. (room temp. limitation, min.) 3183
Setting range Factory setting
0.0 ... 9.9 0.0
Determines how much the ow temperature will be inuenced (increased) if the room temperature is
lower than the desired room temperature (P control).
0.0: The room temperature has no inuence.
9.9: The room temperature has a big inuence.

Table of Contents

Other manuals for Danfoss 087H3241

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss 087H3241 and is the answer not in the manual?

Danfoss 087H3241 Specifications

General IconGeneral
BrandDanfoss
Model087H3241
CategoryController
LanguageEnglish

Related product manuals