Maintenance
Cut-out (limit for heating cut-out) 5179
Setting range Factory setting
OFF / 1 ... 50 °C 18 °C
Set the outdoor temperature limit at which you want the heating system to stop. The
valve closes and after about 3 min. the heating circulation pump stops. ‘Temp. min.
set in line 2177 will be ignored.
Temp. Actual outdoor temp. Accumulated outdoor temp.
18 °C
Time
Heating Heating OFF Heating
This function can save energy by stopping the heating system when the outdoor
temperature gets above a set limit. The heating system switches ON again when the
outdoor temperature and the accumulated outdoor temperature become lower than
the set limit.
The heating cut-out is only active when the controller mode is AUTO (scheduled operation).
When the limit value is set to OFF, there is no heating cut-out.