Definitions
Limitation temperature
Temperature that inuences the desired ow / balance temperature.
Pt 1000 sensor
All sensors used with the ECL Comfort controller are based on the Pt 1000 type. The
resistance is 1000 ohm at 0 °C and it changes with approx. 3.9 ohm / degree.
Optimization
The controller optimizes the start / stop time of the scheduled temperature periods.
Based on the outdoor temperature, the controller automatically calculates when to start
/ stop in order to reach the comfort temperature at the set time. The lower the outdoor
temperature, the earlier the start time. During optimization the comfort / setback
symbol will blink.
Return temperature
The temperature measured in the return can inuence the desired ow temperature.
Room temperature sensor
Temperature sensor placed in the room (reference room, typically the living room) where
the temperature is to be controlled.
Room temperature
Temperature measured by the room temperature sensor, room panel or remote
control. The room temperature can only be controlled directly if a room temperature is
measured. The room temperature can inuence the desired ow temperature.
Schedule
Schedule for periods with comfort and setback temperatures. The schedule can be made
individually for each week day and it consists of 2 comfort periods per day.
Setback temperature
Temperature maintained in the heating / DHW circuit during setback temperature
periods.
Time bar
The time bars illustrate scheduled periods with comfort temperature.
Weather compensation
Flow temperature control based on the outdoor temperature. The control is related to a
user-dened heat curve.
The denitions apply to the Comfort 110 series. Consequently, you might come across
expressions that are not mentioned in your guide.

Table of Contents

Other manuals for Danfoss 087H3241

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss 087H3241 and is the answer not in the manual?

Danfoss 087H3241 Specifications

General IconGeneral
BrandDanfoss
Model087H3241
CategoryController
LanguageEnglish

Related product manuals