Refrigeration is resumed at the same time when all controllers have terminated defrost.
External display AK-UI55
Figure 44: External display AK-UI55
Danfoss
84B8235
(Total length: max. 100 m)
Connections
Table 9: Connection details
AI1
Pressure transmitter
AKS 32R
Connect to terminal 40, 41 and 42.
(Use cable 060G1034: Black=40, Brown=41, Blue=42)
The signal from one pressure transmitter can be received by up to 10 controllers. But only if there are no signicant pressure drops be-
tween the evaporators to be controlled. See Figure 42: AKS 32R info.
AI2 - AI5
Primarily for temperature inputs
S2
Pt 1000 ohm sensor AKS11, placed at the evaporator outlet
S3, S4, S5
Pt 1000 AKS11, PTC 1000 EKS111, NTC5K EKS211 or NTC10K EKS221 sensor or a user-dened sensor type. All have to be of the same
type.
S3, air sensor, placed in the warm air before the evaporator
S4, discharge air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be selected in the conguration)
S5, defrost sensor, placed in the evaporator
(If the DI1 input is used for a temperature measurement, it will appear as AI5.))
DI1
Digital input signal
The dened function is active when the input is short-circuited or opened, depending on the function dened in o02.
DI2
Digital input signal
The dened function is active when the input is short-circuited or opened, depending on the function dened in o37.
AO1
Analogue output signal
Analogue 0 – 10 V (currently not used)
Pulse width modulated signal
Can be used for fast pulse control of rail heat via an external power solid state relay.
MODBUS
For data communication:
Terminal 83 = B-
Terminal 84 = A+
Terminal 85 = screen
Supply voltage
230 V AC or 115 V AC
DO1
AKV valve:
Connection of expansion valve type AKV, AKVA, AKVH or AKVP.
The coil must be a 230 V or 115 V AC coil
Compressor:
Connection of a relay. The coil must be a 230 V or 115 V AC coil. Max. 0.5 A.
Solenoid valve:
The coil must be a 230 V or 115 V AC coil. Max. 0.5 A.
DO2
Alarm:
There is a connection between terminal 10 and 12 in alarm situations and when the controller is without power.
DO2 has reinforced insulation that can be used with 24 V.
Light, Rail heat, Compressor/Liquid line valve:
There is connection between terminal 10 and 11 (10 and 12 at light) when the function is ON.
DO3
Fan:
There is connection between terminal 13 and 14 when the fan is ON.
DO4
Defrost:
There is connection between terminal 15 and 16 when defrosting takes place.
DO2-DO4 + AO1 and
Application 4 / 9
Here, the dierent outputs can be custom dened in q02-q09
© Danfoss | Climate Solutions | 2022.08 BC365212986197en-000201 | 31