Injection control
Table 27: Injection control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip o, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
14=Defrost, 15=Fan delay, 16=Forced closing,
17=Door open, 18=Melt period, 19=Modulating
temp. control, 20=Emergency control, 23=Adaptive
superheat control, 24=Start injection, 25=Manual
control, 26=No refrigerant selected, 29=Case clean-
ing, 30=Forced cooling, 31=Door open, 32=Power-up
delay, 33=Air heating, 45=Shut down controller,
48=Adaptive liquid control
Actual status of output function
Temperature converted from pressure
Readout of actual superheat at the outlet of the evap-
orator
Read out of the actual superheat reference
Actual status of output function
Min. value for the superheat reference
Max. value for the superheat reference
MOP temperature. The valve opening degree is re-
duced until the evaporating temperature reaches the
set MOP limit. If no MOP function is required, select
highest value, which corresponds to OFF
Period time for the pulse width modulation
Min superheat liq-
uid ctrl
Min. value for the superheat reference during adap-
tive liquid control
Max superheat liq-
uid ctrl.
Max. value for the superheat reference during adap-
tive liquid control
Period time for the pulse width modulation
Expert setting - please contact Danfoss for further in-
fo
Expert setting - please contact Danfoss for further in-
fo
Expert setting - please contact Danfoss for further in-
fo
Expert setting - please contact Danfoss for further in-
fo
Expert setting - please contact Danfoss for further in-
fo
Defrost control
Table 28: Defrost control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip o, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
14=Defrost, 15=Fan delay, 16=Forced closing,
17=Door open, 18=Melt period, 19=Modulating
temp. control, 20=Emergency control, 23=Adaptive
superheat control, 24=Start injection, 25=Manual
control, 26=No refrigerant selected, 29=Case clean-
ing, 30=Forced cooling, 31=Door open, 32=Power-up
delay, 33=Air heating, 45=Shut down controller,
48=Adaptive liquid control
Defrost sensor tem-
perature A
Actual temperature of selected defrost stop sensor
© Danfoss | Climate Solutions | 2022.08 BC365212986197en-000201 | 49
AK-CC55 Compact