Fan control
Table 17: Fan control
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
9
Min.value
Max.value
Fact.value
Fan stop high S5 temp.
1-2
F04
*
*
*
*
*
*
*
*
*
-60.0 °C
50.0 °C
50.0 °C
Fan pulsing mode
0=No pulsing, 1=Pulsing
cutout, 2=Pulsing cutout
night
1-2
F05
*
*
*
*
*
*
*
*
*
0
2
0
Fan period time
1-2
F06
*
*
*
*
*
*
*
*
*
1 min
30 min
5 min
Fan ON cycle
1-2
F07
*
*
*
*
*
*
*
*
*
0 %
100 %
100%
Defrost schedule
Table 18: Defrost schedule
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
9
Min.value
Max.value
Fact.value
Defrost schedule
0=No, 1=Yes
1-2
t00
*
*
*
*
*
*
*
*
*
0
1
0
Def. start 1 - Hours
1-2
t01
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 1 - Minutes
1-2
t11
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 2 - Hours
1-2
t02
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 2 - Minutes
1-2
t12
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 3 - Hours
1-2
t03
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 3 - Minutes
1-2
t13
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 4 - Hours
1-2
t04
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 4 - Minutes
1-2
t14
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 5 - Hours
1-2
t05
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 5 - Minutes
1-2
t15
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 6 - Hours
1-2
t06
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Def. start 6 - Minutes
1-2
t16
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Time hours
0-1
t07
*
*
*
*
*
*
*
*
*
0 h
23 h
0 h
Time minutes
0-1
t08
*
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Time date
0-1
t45
*
*
*
*
*
*
*
*
*
1
31
1
Time month
0-1
t46
*
*
*
*
*
*
*
*
*
1
12
1
Time year
0-1
t47
*
*
*
*
*
*
*
*
*
0
100
0
Monday - Follow schedule
0=No, 1=Yes
1-2
t51
*
*
*
*
*
*
*
*
*
0
1
1
Tuesday - Follow schedule
0=No, 1=Yes
1-2
t52
*
*
*
*
*
*
*
*
*
0
1
1
Wednesday - Follow
schedule
0=No, 1=Yes
1-2
t53
*
*
*
*
*
*
*
*
*
0
1
1
Thursday - Follow sched-
ule
0=No, 1=Yes
1-2
t54
*
*
*
*
*
*
*
*
*
0
1
1
Friday - Follow schedule
0=No, 1=Yes
1-2
t55
*
*
*
*
*
*
*
*
*
0
1
1
Saturday - Follow sched-
ule
0=No, 1=Yes
1-2
t56
*
*
*
*
*
*
*
*
*
0
1
1
Sunday - Follow schedule
0=No, 1=Yes
1-2
t57
*
*
*
*
*
*
*
*
*
0
1
1
Miscellaneous
Table 19: Miscellaneous
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
9
Min. value
Max. value
Fact. value
Delay of outputs at power
up
1-2
o01
*
*
*
*
*
*
*
*
*
0 s
600 s
5s
DI1
Conguration
0=None, 1=DI status,
2=Door function, 3=Door
alarm, 4=Defrost start,
5=Main switch, 6=Night
setback, 7=Thermostat
band, 8=Alarm at closed,
9=Alarm at open, 10=Case
cleaning, 11=Forced cool-
ing, 12=Open blinds,
14=Forced closing,
15=Shutdown, 16=Light
control, 20=Leak detec-
tion, 21=Adaptive liquid
control, 29=Door fan stop
1-2
(1)
o02
*
*
*
*
0
29
0
Network address
1-3
(1)
o03
*
*
*
*
*
*
*
*
*
0
240
0
© Danfoss | Climate Solutions | 2022.08 BC365212986197en-000201 | 39