Minimum time the compressor has to be stopped
Time delay for couplings of two compressors. The
step delay is the time that has to elapse from the rst
compressor cuts in and until the next compressor can
cut in.
Selection of step control mode for compressors. At se-
quential mode compressor 1 will always be the rst to
start and the last to stop. In cyclic mode the run time
between the compressor will be equalized.
Select whether compressor 2 is to be in operation in
thermostat band 2
Fan control
Table 31: Fan control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip o, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
14=Defrost, 15=Fan delay, 16=Forced closing,
17=Door open, 18=Melt period, 19=Modulating
temp. control, 20=Emergency control, 23=Adaptive
superheat control, 24=Start injection, 25=Manual
control, 26=No refrigerant selected, 29=Case clean-
ing, 30=Forced cooling, 31=Door open, 32=Power-up
delay, 33=Air heating, 45=Shut down controller,
48=Adaptive liquid control
Actual status of output function
Actual status of output function
Pulse operation of fan 0: No pulse operation 1: Pulse
operation when the thermostat is cut out2: Pulse op-
eration when the thermostat is cut out, but only dur-
ing night operation
0=No pulsing, 1=Pulsing cutout, 2=Pulsing cutout
night
Periodtime for pulsing of fan
ON time for fan. The ON period is set as a percentage
of the period time
Fan stop temperature The function stops the fans in
an error situation, so that they will not provide power
to the appliance. If the defrost sensor registers a high-
er temperature than the one set here, the fans will be
stopped. There will be re-start at 2 K below the set-
ting. The function is not active during a defrost or
start-up after a defrost.
You can set whether fans should be operational or
stopped if the function "Forced closing" is activated
here. 0: Fans are OFF1: Fans are ON2: Fans are OFF and
defrost is not permitted3: Fans are ON and defrost is
not permitted
0=OFF, 1=ON, 2=OFF and suppress defrost, 3=ON and
suppress defrost
Fan stop at blinds
closing
When blinds are closing the fans are stopped in the
dened time delay in order to ensure that the blinds
are closed correctly
Railheat control
Table 32: Railheat control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip o, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
14=Defrost, 15=Fan delay, 16=Forced closing,
17=Door open, 18=Melt period, 19=Modulating
temp. control, 20=Emergency control, 23=Adaptive
superheat control, 24=Start injection, 25=Manual
control, 26=No refrigerant selected, 29=Case clean-
ing, 30=Forced cooling, 31=Door open, 32=Power-up
delay, 33=Air heating, 45=Shut down controller,
48=Adaptive liquid control
Actual dewpoint received from system manager via
network
Actual status of output function
Readout of the actual rail power in %
Actual status of output function
AK-CC55 Compact