Miscellaneous - Pri-
ority
Select the priority of the alarms associated to the
alarm group. Be aware - by selecting "Disable" the
alarms will not be shown on the display or be routed
to the alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
Select the priority of the alarms associated to the
alarm group. Be aware - by selecting "Disable" the
alarms will not be shown on the display or be routed
to the alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
Control stopped -
Priority
Select the priority of the alarms associated to the
alarm group. Be aware - by selecting "Disable" the
alarms will not be shown on the display or be routed
to the alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
Leak detection - Pri-
ority
Select the priority of the alarms associated to the
alarm group. Be aware - by selecting "Disable" the
alarms will not be shown on the display or be routed
to the alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
Miscellaneous
Table 36: Miscellaneous → Access codes
Access code for local display
Access code for local display
Access code for local display
Table 37: Miscellaneous → Network
Quality of the network communication
Network address of the controller
Communication speed of network
1=Auto, 2=9600 Baud, 3=19200 Baud, 4=38400 Baud
Select parity and stop bit of Modbus messages
Table 38: Miscellaneous → Sensor adjustment
S2 Gas outlet A - Ad-
justment
Correction of sensor signal e.g. due to long sensor ca-
ble
S3 Air ON evap. A -
Adjustment
Correction of sensor signal e.g. due to long sensor ca-
ble
S4 Air OFF evap. A -
Adjustment
Correction of sensor signal e.g. due to long sensor ca-
ble
S5 Evaporator A -
Adjustment
Correction of sensor signal e.g. due to long sensor ca-
ble
Table 39: Miscellaneous → Factory reset
With this command you save the controller’s actual
settings as a new basic setting (the earlier factory set-
tings are overwritten).
Reset to factory set-
tings
Command which will revert all controller settings to
factory values.
Advanced
Table 40: Advanced → Advanced injection control
Select how to control the superheat of the evapora-
tor. At adaptive control the superheat reference is
adapted automatically to give the best utilization of
the evaporator surface. At load based control the su-
perheat reference is increased at high loads
Minimum superheat limit where the valve is closing
Expert setting - contact Danfoss for further informa-
tion
Min limit for 
amplication factor of PI controller ad-
justing the valve opening degree (expert setting)
Max limit for 
amplication factor of PI controller ad-
justing the valve opening degree (expert setting)
© Danfoss | Climate Solutions | 2022.08 BC365212986197en-000201 | 55
AK-CC55 Compact