EasyManua.ls Logo

Danfoss AK-CC55 Compact - Product Specification; Technical Data; Electrical Specifications; Sensor and Measuring Data

Danfoss AK-CC55 Compact
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product specication
Technical data
Electrical specications
Table 44: Electrical specications
Electrical data
Value
Supply voltage AC [V]
115 V / 230 V, 50/60 Hz
Power consumption [VA]
5 VA
Power ON indicator
Green LED
Electrical cable dimensioning [mm
2
]
Max. 1.5 mm
2
multi-core cable
Sensor and measuring data
Table 45: Sensor and measuring data
Sensor and measuring data
Value
Sensor S2
Pt 1000 AKS11
Sensor S3, S4, S5
Pt 1000 AKS11
PTC 1000 EKS111
NTC5K EKS211
NTC10K EKS221 sensor
(All 3 must be of the same type)
Temperature measuring accuracy
Pt1000: -60 – 120 °C. ±0.5 K
PTC1000: -60 – 80 °C. ±0.5 K
NTC5K: -40 – 80 °C. ±1.0 K
NTC10K: -40 – 120 °C. ±1.0 K
Pt1000 sensor specication
±0.3 K at 0 °C
±0.005 K per degree
Pe measuring
AKS 32R Ratiometric pressure transmitter: 10-90%
Input and output relay specications
Table 46: Input and output relay specications
Input and output relay
specications
Input/output
Description
Digital input
DI1
DI2
Signal from dry contact functions
Requirements to contacts: Gold plating
Cable length must be max. 15 m
Use auxiliary relays when the cable is longer
Open loop: 12 V (SELV)
Contact 3.5 mA
Solid state output
DO1 (for AKV coil)
115V / 230 V AC
Max. 0.5 A (No overload protection!)
Max. 1 x 20 W AKV for 115 V AC
2 x 20 W AKV for 230 V AC
Note: 2 EC coils are not supported.
Relays
DO2
DO3
DO4
115 V / 230 V AC
Load max.: CE. 8 (6)A
UL. 8A res. 3FLA 18LRA
Load min.: 1VA
Inrush: DO2 DO3 TV-5 80A
Analogue output/ PWM
AO1
0 / 10 V Pulse Width Modulated
(PWM) max. 15 mA.
0 – 10 V variable, max. 2 mA
NOTE:
DO2 to DO4 are 16 A relays.
Max. load must be observed.
DO2 / DO3 is recommended for load with high inrush current e.g. EC Fan and LED light.
All relays are sealed for use with ammable refrigerant like Propane R290.
Compliance with EN 60 335-2-89: 2010 Annex BB.
© Danfoss | Climate Solutions | 2022.08 BC365212986197en-000201 | 59
AK-CC55 Compact

Table of Contents