Fan control during
defrost
Fan operation during defrost Here you can set how
the fan is to operate during defrost.0: Stopped (Runs
during pump down)1: Running (stopped during "fan
delay")2: Running during pump down and defrost. Af-
ter that stopped3: Running during pump down and
defrost until defrost stop sensor reaches fan stop tem-
perature limit
0=OFF, 1=ON, 2=OFF at drip, 3=OFF at high temp
Delay of fan start after defrost. Here you set the time
that is to elapse from compressor start after a defrost
and until the fan may start again. (The time when re-
maining water is transformed into ice on the evapora-
tor).
Temperature limit for starting the fans after a defrost.
When the measured S5 evaporator temperature is
getting below the set limit, the fans are started
If the fan control during defrost has been set up for it,
the fans can be stopped during the defrost if the de-
frost sensor exceeds the set temperature limit
Rail heat during de-
frost
Dene how railheat is controlled during defrost0: Rail-
heat is OFF all the time1: Railheat is ON all the time2:
Normal railheat control
0=OFF, 1=ON, 2=Normal control
Display delay after
defrost
Set the maximum time the display should show the
defrost code "-d-" after a defrost. The normal temper-
ature readout is normally started when the tempera-
ture in the case is OK again or if a high temperature
alarm is raised.
Defrost schedules
Table 29: Defrost schedules
Wednesday - Follow
schedule
Thursday - Follow
schedule
Saturday - Follow
schedule
Compressor
Table 30: Compressor
Actual status of output function
Actual status of output function
Minimum time the compressor is to run once it has
been started.