Time delay on transition from refrigeration phase to
heating phase (there is not time delay on transition
from heating phase to refrigeration phase)
Melt function. Only for control of MT cases/rooms (-5
to +10°C). The function ensures that the evaporator
will not be blocked by ice crystals. Here you set how
often the function is to stop the refrigeration and
hence transform the ice crystals to water.
Melt period. Here you set how long an on-going melt
function is to last
Alarm limits and delays
Table 26: Alarm limits and delays
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip o, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
14=Defrost, 15=Fan delay, 16=Forced closing,
17=Door open, 18=Melt period, 19=Modulating
temp. control, 20=Emergency control, 23=Adaptive
superheat control, 24=Start injection, 25=Manual
control, 26=No refrigerant selected, 29=Case clean-
ing, 30=Forced cooling, 31=Door open, 32=Power-up
delay, 33=Air heating, 45=Shut down controller,
48=Adaptive liquid control
Measured temperature for alarm thermostat
Readout of actual high alarm limit for the tempera-
ture monitoring
Readout of actual low alarm limit for the temperature
monitoring
Command for resetting all alarms, unless they are still
active
Signal to the alarm thermostat Here you have to de-
ne the ratio between the sensors which the alarm
thermostat has to use. S3, S4 or a combination of the
two. With setting 0% only S3 is used. With 100% only
S4 is used
Upper alarm limit. The limit value is set in absolute
value. The limit value will be raised with the night o-
set during night operation.
Lower alarm limit. The limit value is set in absolute
value
Upper alarm limit. The limit value is set in absolute
value. The limit value will be raised with the night o-
set during night operation.
Lower alarm limit. The limit value is set in absolute
value
Alarm delay (short alarm delay on air temperature). If
the upper or the lower alarm limit values are excee-
ded, a timer function will commence. The alarm will
not become active until the set time delay has been
passed. The time delay is set in minutes
Alarm delay at tempeature pulldown conditions (long
alarm delay). This time delay is used during start-up,
during defrost, immediately after a defrost. There will
be change-over to the normal time delay when the
temperature has dropped below the set upper alarm
limit.
Time delay for door alarm
Start of refrigeration when door is open. If the door
has been left open, refrigeration will be started after
the set time.
Time delay for digital input alarm
Time delay for digital input alarm