Status at the day-/night operation (night operation:
on/o)
Readout of the actual cutin value for the thermostat
Readout of the actual cut out value for the thermostat
Read the ongoing cutin time for the thermostat or the
duration of the last completed cutin
Readout of which thermostat used for regulation: 1=
Thermostat band 12= Thermostat band 2
Actual status of output function
Here it is dened how the thermostat is to operate. Ei-
ther as an ordinary ON/OFF thermostat or as a modu-
lating thermostat.When operation is ”modulating” the
valve will limit the ow of refrigerant so that the tem-
perature variation will be less than for the ON/OFF
thermostat.The thermostat dierential (r01) must not
be set lower than 2K for ""modulating"".In a decentral-
ised plant you must select the ON/OFF thermostat
setting."
Set point. The thermostat’s cutout value when the
given thermostat band is in use
When the temperature is higher than the set cutout +
the set dierential, the compressor relay will be cut in.
It will cut out again when the temperature comes
down to the set cutout limit
Set point. The thermostat’s cutout value when the
given thermostat band is in use
When the temperature is higher than the set cutout +
the set dierential, the compressor relay will be cutin.
It will cutout again when the temperature comes
down to the set cut-out limit
Setpoint limitation - The controller’s setting range for
the thermostat setpoint may be narrowed down, so
that much too high or much too low values are not
set accidentally - with resulting damages.To avoid a
too high setting of the setpoint, the max. allowable
reference value may be lowered
Setpoint limitation - The controller’s setting range for
the thermostat setpoint may be narrowed down, so
that much too high or much too low values are not
set accidentally - with resulting damages.To avoid a
too low setting of the setpoint, the min. allowable ref-
erence value may be increased
Selection of thermostat sensor. Here you dene the
sensor the thermostat is to use for its control function.
S3, S4, or a combination of them. With the setting 0%,
only S3 is used. With 100%, only S4.
Thermostat sensor
S4 % night
Selection of thermostat sensor S4% during night op-
eration with night blinds. Here you dene the sensor
the thermostat is to use for its control function. S3, S4,
or a combination of them. With the setting 0%, only
S3 is used. With 100%, only S4.
Night setback value.The thermostat’s reference will be
the setpoint plus this value when the controller
changes over to night operation.
Frost protection on S4 air temperature. If the S4 tem-
perature sensors measures a temperature lower than
the set limit, refrigeration will be stopped in order to
protect produce from ice formation. Refrigeration will
start again when the S4 temperature has risen 2K
above the set limit
Heat function. Set the width of the Neutral Zone for
changeover from cooling to heating "