Integration time of PI controller adjusting the valve
opening degree (expert setting)
Setting of required stability of S2 gas outlet tempera-
ture before the superheat reference is reduced (Ex-
pert setting)A higher value will allow more instabillity
in S2 signalA lower value will allow less instabillity in
S2 signal
Expert injection setting - contact Danfoss for further
information
Gain factor for feedback of evaporating temperature
signal Te to PI controller controlling the superheat
(expert setting)
Amplication factor for modulating temperature con-
trol (Expert setting)
Integration time for modulating temperature control
(Expert setting)
Expert readout - contact Danfoss for further informa-
tion
Calculated maximum opening degree of injection
valve (expert readout)
Superheat close liq-
uid ctrl. A
Minimum limit of superheat where the valve is clos-
ing duting adaptive liquid control
Average opening degree of liquid line solenoid valve
during day operation
Average opening degree of liquid line solenoid valve
during night operation
Expert injection setting - contact Danfoss for further
information
Expert setting - contact Danfoss for further informa-
tion
Expert injection setting - contact Danfoss for further
information
Expert injection setting - contact Danfoss for further
information
Readout showing which part of the injection function
that is in control of the valve opening degree
Values must be changed as per below:
0=Adaptive SH control
1=MOP
2=Superheat close
3=MTR
Table 41: Advanced → Master control
Readout of the actual control state of the controller
0=Main switch OFF, 1=Injection start, 2=Superheat
ctrl., 3=Fill evap., 4=Defrost, 5=Post defrost, 6=Forced
closing, 7=Injection fault, 8=Emergency control,
9=Modulating ctrl., 10=Melt period, 11=Door open,
12=Case cleaning, 13=Cutout, 14=Forced cooling,
15=Shut down
Master control signal used for switching case load
ON/OFF depending on load condition
0=No action, 1=Toggle ON, 2=Toggle OFF
Master control signal used to control load balance be-
tween multiple case controllers on the same suction
line
Requested oset to actual evporating temperature in
order to keep the air temperature at the actual set
point
Master control signal allowing switch to adaptive liq-
uid control
Master control signal for changing between day and
night time operation
Master control signal used to shut down a case for a
time period. During shut down there will be no alarm
monitoring
Master control signal that will close the injection
valve
Master control signal that will provide forced cooling
AK-CC55 Compact
© Danfoss | Climate Solutions | 2022.08 BC365212986197en-000201 | 56