Danfoss AK-CC55 Compact - Page 56

Danfoss AK-CC55 Compact
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function
Description
Values
Code
Short name
Superheat Tn A
Integration time of PI controller adjusting the valve
opening degree (expert setting)
x72
--- SH Tn
S2 stabillity A
Setting of required stability of S2 gas outlet tempera-
ture before the superheat reference is reduced (Ex-
pert setting)A higher value will allow more instabillity
in S2 signalA lower value will allow less instabillity in
S2 signal
Y33
--- S2 Stability
S2 Std deviation
Expert injection setting - contact Danfoss for further
information
Y34
--- S2 Std Dev
Te feedback gain A
Gain factor for feedback of evaporating temperature
signal Te to PI controller controlling the superheat
(expert setting)
x73
--- Te-gain
Kp MTR control A
Amplication factor for modulating temperature con-
trol (Expert setting)
x77
--- MTR Kpfactor
Tn MTR control A
Integration time for modulating temperature control
(Expert setting)
x78
--- MTR Tn sec
AFident A
Expert readout - contact Danfoss for further informa-
tion
x79
--- AFident
Calculated Max OD
A
Calculated maximum opening degree of injection
valve (expert readout)
x80
--- Max OD %
Superheat close liq-
uid ctrl. A
Minimum limit of superheat where the valve is clos-
ing duting adaptive liquid control
x87
--- SH close Liq
Emergency OD day
Average opening degree of liquid line solenoid valve
during day operation
z01
--- EmerC OD day
Emergency OD
night
Average opening degree of liquid line solenoid valve
during night operation
z02
--- EmerC OD ngt
SH Band
Expert injection setting - contact Danfoss for further
information
Y28
--- SH Band
Injection duty cycle
SP
Expert setting - contact Danfoss for further informa-
tion
Y29
--- ThDutyCycle
Injection duty cycle
Expert injection setting - contact Danfoss for further
information
Y30
--- ActDutyCycle
P-gain
Expert injection setting - contact Danfoss for further
information
Y31
--- P - Gain
OD Ctrl. status
Readout showing which part of the injection function
that is in control of the valve opening degree
Values must be changed as per below:
0=Adaptive SH control
1=MOP
2=Superheat close
3=MTR
Y32
--- OD Status
Table 41: Advanced Master control
Function
Description
Values
Code
Short name
Regulation condi-
tion A
Readout of the actual control state of the controller
0=Main switch OFF, 1=Injection start, 2=Superheat
ctrl., 3=Fill evap., 4=Defrost, 5=Post defrost, 6=Forced
closing, 7=Injection fault, 8=Emergency control,
9=Modulating ctrl., 10=Melt period, 11=Door open,
12=Case cleaning, 13=Cutout, 14=Forced cooling,
15=Shut down
x62
--- Reg. Cond.
MC Actual cutin
temp.
x63
--- Cutin temp.
MC Actual cutout
temp.
x64
--- Cutout temp.
MC Ther. toggle
Master control signal used for switching case load
ON/OFF depending on load condition
0=No action, 1=Toggle ON, 2=Toggle OFF
x81
--- TherToggle
MC Load request
Master control signal used to control load balance be-
tween multiple case controllers on the same suction
line
x82
--- LoadReq
MC Max Te oset
Requested oset to actual evporating temperature in
order to keep the air temperature at the actual set
point
x84
--- MaxTeOset
MC Liquid control
Master control signal allowing switch to adaptive liq-
uid control
0=OFF, 1=ON
x85
--- MC Liq. Ctrl
MC Night setback
Master control signal for changing between day and
night time operation
0=OFF, 1=ON
x06
--- Night setbck
MC Case shutdown
Master control signal used to shut down a case for a
time period. During shut down there will be no alarm
monitoring
0=OFF, 1=ON
x17
--- Case shutdwn
MC Forced closing
Master control signal that will close the injection
valve
0=OFF, 1=ON
x07
--- Forced close
MC Forced cooling
Master control signal that will provide forced cooling
0=OFF, 1=ON
x08
--- Forced cool.
AK-CC55 Compact
© Danfoss | Climate Solutions | 2022.08 BC365212986197en-000201 | 56