Function
Values
R-W
Code
1
2
3
4
5
6
7
8
9
Min. value
Max. value
Fact. value
Access code 3
3-3
o05
*
*
*
*
*
*
*
*
*
0
999
0
Temperature sensor type
0=Pt 1000, 1=PTC 1000,
2=NTC 5k, 3=NTC 10k,
4=User-dened
1-3
(1)
o06
*
*
*
*
*
*
*
*
*
0
4
0
Max hold time
1-2
o16
*
*
*
*
*
*
*
*
*
0 min
360 min
20 min
Display air S4%
1-2
o17
*
*
*
*
*
*
*
*
*
0 %
100 %
100%
Pe Min range
1-3
(1)
o20
*
*
*
*
*
-1.0 Bar
5.0 Bar
-1.0Bar
Pe Max range
1-3
(1)
o21
*
*
*
*
*
6.0 Bar
200.0 Bar
12.0Bar
Refrigerant
0=Not seleted, 6=R13,
7=R13b1, 2=R22, 8=R23,
14=R32, 11=R114,
3=R134a, 12=R142b,
24=R170, 15=R227,
25=R290, 16=R401A,
18=R402A, 19=R404A,
21=R407A, 22=R407B,
20=R407C, 37=R407F,
49=R407H, 23=R410A,
32=R413A, 30=R417A,
31=R422A, 33=R422D,
34=R427A, 35=R438A,
40=R448A, 41=R449A,
48=R449B, 43=R450A,
44=R452B, 45=R454B,
9=R500, 4=R502,
10=R503, 17=R507,
36=R513A, 26=R600,
27=R600a, 5=R717,
28=R744, 46=R1233zdE,
38=R1234ze, 39=R1234yf,
47=R1234zeZ, 29=R1270,
42=R452A, 1=User de-
ned display, 13=User de-
ned
1-3
(1)
o30
*
*
*
*
*
0
49
0
DI2 Conguration
0=None, 1=DI status,
2=Door function, 3=Door
alarm, 4=Defrost start,
5=Main switch, 6=Night
setback, 7=Thermostat
band, 8=Alarm at closed,
9=Alarm at open, 10=Case
cleaning, 11=Forced cool-
ing, 12=Open blinds,
13=Coordinated defrost,
14=Forced closing,
15=Shutdown, 16=Light
control, 20=Leak detec-
tion, 21=Adaptive liquid
control, 29=Door fan stop
1-2
(1)
o37
*
*
*
*
*
*
*
*
*
0
29
0
Light control mode
1=Day and night, 2=Net-
work, 3=Door switch,
4=Network (Fallback),
5=Digital input
1-2
o38
*
*
*
*
1
5
1
MC Light signal
0=OFF, 1=ON
1-2
o39
*
*
*
*
0
1
0
Rail heat ON cycle day
1-2
o41
*
*
*
*
*
*
*
*
*
0 %
100 %
100%
Rail heat ON cycle night
1-2
o42
*
*
*
*
*
*
*
*
*
0 %
100 %
100%
Rail heat period time
1-2
o43
*
*
*
*
6 min
60 min
6min
Case cleaning mode
0=OFF, 1=Fans run,
2=Cleaning
0-1
o46
*
*
*
*
*
*
*
*
*
0
2
0
Application mode
1=1. Comp/Alarm/Fan/
Defrost, 2=2. Comp/
Light/Fan/Defrost, 3=3.
Comp/Railheat/Fan/
Defrost, 4=4. Comp/
Custom, 5=5. EEV/
Comp/Fan/Defrost, 6=6.
EEV/Alarm/Fan/Defrost,
7=7. EEV/Light/Fan/
Defrost, 8=8. EEV/
Rail/Fan/Defrost, 9=9.
EEV/Custom
1-3
(1)
o61
*
*
*
*
*
*
*
*
*
1
9
5
Access code 2
2-2
o64
*
*
*
*
*
*
*
*
*
0
999
0
Make new factory
0=OFF, 1=ON
3-3
(1)
o67
*
*
*
*
*
*
*
*
*
0
1
0
Rail heat control mode
0=ON, 1=Day/Night timer,
2=Dew point ctrl.
1-2
o85
*
*
*
*
*
*
*
*
*
0
2
0