EasyManua.ls Logo

Danfoss AK-CC55 Compact - Page 36

Danfoss AK-CC55 Compact
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
Open parameter r89 and set the number for the array of presettings. The few selected settings will now be
transferred to the menu
Set the desired cut-out temperature r00
Set the weighted thermostat air temperature between S4 and S3 sensor r15
Set the weighted thermostat air temperature between S4 and S3 during night operation r61
Set the weighted alarm air temperature between S4 and S3 A36
Set the weighted display readout between S4 and S3 o17
Select refrigerant via parameter o30 (only application 5-9)
Set the pressure transmitter min. and max. range via parameter o20 and o21 (only application 5-9)
Set the desired defrost method in d01
Set the interval time between defrost starts in d03
Set the desired defrost sensor in d10
Set the maximum defrost time in d04
Set the defrost stop temperature in d02
Open parameter r12 and start the regulation
Go through the parameter list and change the factory values where needed
Get the controller up and running on network:
MODBUS: Activate scan function in system unit
Table 11: Food type settings
Setting of presettings (r89).
After setting 1-5, setting is returned to 0.
1
2
3
4
5
Food type
Vegetables
Milk
Meat/sh
Frozen food
Ice cream
Temperature (r00)
8 °C
0 °C
-2 °C
-20 °C
-24 °C
Max. temp. setting (r02)
10 °C
4 °C
2 °C
-16 °C
-20 °C
Min. temp. setting (r03)
4 °C
-4 °C
-6 °C
-24 °C
-28 °C
Upper alarm limit (A13)
14 °C
8 °C
8 °C
-15 °C
-15 °C
Lower alarm limit (A14)
0 °C
-5 °C
-5 °C
-30 °C
-30 °C
Upper alarm limit for S6 (A22)
14 °C
8 °C
8 °C
-15 °C
-15 °C
Lower alarm limit for S6 (A23)
0 °C
-5 °C
-5 °C
-30 °C
-30 °C
AK-CC55 Compact
© Danfoss | Climate Solutions | 2022.08 BC365212986197en-000201 | 36

Table of Contents

Related product manuals