26
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
7.2 Alarms / ALA
ERC menu
code
Default Min Max Unit
Conv
Unit Scale Default Access
Shop Ser OEM
Alarm ALA
High Alarm delay Htd 30 0 240 no min 1 -- RW RW
Low Alarm delay Ltd 0 0 240 no min 1 -- RW RW
High Temp Alarm HAt 15.0/59.0 -50.0/-58.0 80.0/176.0 C/Fa °C/°F .1 -- RW RW
Low Temp Alarm LAt -50.0/-58.0 -50.0/-58.0 80.0/176.0 C/F a °C/°F .1 -- RW RW
Pulldown delay Pdd 240 0 960 no min 1 -- RW RW
Door Open delay dod 2 0 60 no min 1 -- RW RW
Alarm Buzzer Duration Abd 0 0 999 no min 1 -- RW RW
Auto Clearance of
Alarm/Error
ACA yES no yES no 1 -- RW RW
ERC
102 Reference manual – 7 PARAMETERS