46
ERC menu
code
Description
Defrost dEF Defrost Settings
Def. type dFt no: Defrost function is disabled
EL: Electrical or time defrost
Hgd: Hot gas defrost (contact Danfoss for details)
nat:Off-cycle defrost (natural defrost)
Def terminate temp dtt Temperature at which defrost cycle will stop
Def Min Interval dii The minimum time in hours between the start of each defrost cycle
Def Max Interval dAi The maximum time in hours between the start of each defrost cycle
Def Min Time dit The minimum duration of a defrost cycle in minutes
Def Max time dAt The maximum duration of a defrost cycle in minutes
Drip off time dot The duration in minutes of the drip-off time at the end of a defrost cycle
Fan delay after Defrost Fdd The duration in minutes before the fan starts after a defrost cycle
Fan start Temp Ftd The temperature at which the fan will start after a defrost
Defrost Fan on dFA Whether the fan will run during a defrost cycle
Initial Defrost Interval idi The number of hours after power-up before the first defrost cycle starts
Defrost on compressor
time
dCt Whether the defrost cycles are measured by elapsed time (nO) or compressor run time (yES)
ERC menu
code
Description
Fan FAn Fan settings
Fan always On FAo nO: fan parameters below active. yES: Fan is always on
Fan On Delay Fod Delay in seconds before fan starts after compressor starts
Fan Stop delay FSd Delay in seconds before fan stops after compressor stops
Fan On Cycle FoC The number of seconds the fan runs when the compressor is off
Fan Stop Cycle FSC The number of seconds the fan does not run when the compressor is off
ERC menu
code
Description
Energy management Eng Energy Management
Shop Light Day SLd When ambient light is above this level, Eco mode is cancelled. Requires light sensor
Shop Light Night SLn When ambient light is below this level, Eco mode is enabled. Requires light sensor
Eco Activity delay EAd Minutes delay after last door opening until ECO mode is enabled; 0: disable
Eco Light delay ELd Delay [min] between detection of shop light on/off and ECO mode activation / suspension
Eco Temperature Offset Eto Temperature increase for Eco mode relative to normal mode
ERC
102 Reference manual – APPENDIX I: PARAMETER QUICK LIST