Manual initialization
NOTICE!
When carrying out manual initialization, serial communi-
cation, RFI lter settings and fault log settings are reset.
Manual initialization removes parameters selected in
parameter 0-25 My Personal Menu.
1. Disconnect from the line power and wait until
the display turns o.
2. Press
2a [Status] - [Main Menu] - [OK] at the
same time while powering up for the
LCP 102, graphical LCP.
2b [Menu] while powering up for LCP 101,
numerical LCP.
3. Release the keys after 5 s.
4. The adjustable frequency drive is now
programmed according to default settings.
This parameter initializes all except:
Parameter 15-00 Operating hours
Parameter 15-03 Power-ups
Parameter 15-04 Over Temps
Parameter 15-05 Over Volts