5.2.4 0-4* LCP Keypad
Enable, disable and password protect individual keys on the
LCP.
0-40 [Hand on] Key on LCP
Option: Function:
[0] Disabled No function
[1] * Enabled [Hand on] Key enabled
[2] Password Avoid unauthorized start in Hand
mode. If 0-40 [Hand on] Key on LCPis
included in the My Personal Menu,
then define the password in
0-65 Personal Menu Password.
Otherwise define the password in
0-60 Main Menu Password.
[3] Enabled without
OFF
[4] Password without
OFF
[5] Enabled with OFF
[6] Password with OFF
0-41 [Off] Key on LCP
Option: Function:
[0] Disabled Avoids accidental stop of the AFE.
[1] * Enabled
[2] Password Avoids unauthorised stop. If par. 0-41 is included
in the Quick Menu, then define the password in
par. 0-65 Quick Menu Password.
0-42 [Auto on] Key on LCP
Option: Function:
[0] Disabled avoid accidental start of the AFE in Auto mode.
[1] * Enabled
[2] Password Avoids unauthorised start in Auto mode. If par.
0-42 is included in the Quick Menu, then define
the password in par. 0-65 Quick Menu Password.
0-43 [Reset] Key on LCP
Option: Function:
[0] * Disabled No effect when [Reset] is pressed. Avoids
accidental alarm reset.
[1] * Enabled
[2] Password
Avoids unauthorised resetting. If
0-43 [Reset] Key on LCP is included in the
Quick Menu, then define the password in
0-65 Quick Menu Password.
[7] Enabled
without OFF
Resets the AFE without setting it in Off
mode.
[8] Password
without OFF
Resets the AFE without setting it in Off
mode. A password is required when
pressing [Reset] (see [2]).
5.2.5 0-5* Copy / Save
Copy parameter settings between set-ups and to/from the
LCP.
0-50 LCP Copy
Option: Function:
[0] * No copy
[1] All to LCP
[2] All from LCP
[3] Size indep. from LCP
0-51 Set-up Copy
Option: Function:
[0] * No copy No function
[1] Copy to set-up 1
[2] Copy to set-up 2
[3] Copy to set-up 3
[4] Copy to set-up 4
[9] Copy to all
5.2.6 0-6* Password
0-60 Main Menu Password
Range: Function:
100 N/A* [0 - 999 N/
A]
Define the password for access to the Main
Menu via the [Main Menu] key. If
0-61 Access to Main Menu w/o Password is
set to Full access [0], this parameter will be
ignored.
0-61 Access to Main Menu w/o Password
Option: Function:
[0] * Full access
Disables password defined in 0-60 Main
Menu Password.
[1] LCP: Read only Prevent unauthorized editing of Main Menu
parameters.
[2] LCP: No access Prevent unauthorized viewing and editing of
Main Menu parameters.
[3] Bus: Read only Read-only functions for parameters on
fieldbus and/or FC standard bus.
[4] Bus: No access No access to parameters is allowed via
fieldbus and/or FC standard bus.
[5] All: Read only Read-only function for parameters on LCP,
fieldbus or FC standard bus.
[6] All: No access No access from LCP, fieldbus or FC standard
bus is allowed.
If Full access [0] is selected then 0-60 Main Menu Password,
0-65 Personal Menu Password and 0-66 Access to Personal
Menu w/o Password will be ignored.