10.5 Fuses and Circuit Breakers
Fuses ensure that possible damage to the drive is limited to damages inside the drive. To ensure compliance with EN 50178,
use the recommended fuses as replacements. Use of fuses on the supply side is mandatory for IEC 60364 (EC) and NEC 2009
(UL) compliant installations.
Branch circuit protection
To protect the installation against electrical and re hazard, all branch circuits in an installation, such as those branch circuits
found in switchgear and machines, must be protected against short circuit and overcurrent according to national/interna-
tional regulations.
Fuses or circuit breakers are mandatory to comply with IEC 60364.
Enclosure Model Recommended
fuse size
Recommended
maximum fuse
E P315
P355
P400
P450
aR-900
aR-900
aR-900
aR-900
aR-900
aR-900
aR-900
aR-900
F P500
P500
P560
P630
P710
P1000
aR-1600
aR-2000
aR-2500
aR-2500
aR-2500
aR-2500
aR-1600
aR-2000
aR-2500
aR-2500
aR-2500
aR-2500
Table 10.10 Recommended Fuses for CE Compliance, 380–480 V
Enclosure Model Recommended
fuse size
Recommended
maximum fuse
E P450
P500
P560
P630
aR-700
aR-900
aR-700
aR-900
F P710
P800
P900
P1M0
P1M2
P1M4
aR-1600
aR-2000
aR-2500
aR-1600
aR-2000
aR-2500
Table 10.11 Recommended Fuses for CE Compliance, 525–690 V
Electrical Installation Con... Design Guide
MG16C302 Danfoss A/S © 11/2017 All rights reserved. 177
10 10

Table of Contents

Other manuals for Danfoss VLT AHF 005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AHF 005 and is the answer not in the manual?

Danfoss VLT AHF 005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AHF 005
CategoryDC Drives
LanguageEnglish