1
2
z
z
z
L1
L2
L3
PE
U
V
W
C
S
I
2
I
1
I
3
I
4
C
S
C
S
C
S
C
S
I
4
C
S
z
PE
3
4
5
6
1 Ground wire Cs Possible shunt parasitic capacitance paths (varies with dierent
installations)
2 Shield I1 Common-mode leakage current
3 AC mains supply I2 Shielded motor cable
4 Drive I3
Safety ground (4
th
conductor in motor cables)
5 Shielded motor cable I4 Unintended common-mode current
6 Motor – –
Illustration 10.26 Electric Model Showing Possible Leakage Currents
10.15.1 EMC Test Results
The following test results have been obtained using a drive (with options if relevant), a shielded control cable, a control box
with potentiometer, a motor, and motor shielded cable.
RFI lter type Conducted emission Radiated emission
Standards and
requirements
EN 55011 Class B
Housing,
trades, and
light
industries
Class A
group 1
Industrial
environme
nt
Class A
group 2
Industrial
environment
Class B
Housing,
trades, and
light industries
Class A group 1
Industrial
environment
Class A group 2
Industrial
environment
EN/IEC 61800-3 Category C1
First
environment
Home and
oce
Category
C2
First
environme
nt Home
and oce
Category C3
Second
environment
Industrial
Category C1
First
environment
Home and
oce
Category C2
First environment
Home and oce
Category C3
First environment
Home and oce
H2
FC 102 355–1000 kW 380–
480 V
No No 150 m
(492 ft)
No No Yes
450–1400 kW 525–
690 V
No No 150 m
(492 ft)
No No Yes
H4
FC 102 355–1000 kW 380–
480 V
No 150 m
(492 ft)
150 m
(492 ft)
No Yes Yes
450–1400 kW 525–
690 V
– – – – – –
Table 10.39 EMC Test Results (Emission and Immunity)
Electrical Installation Con...
VLT
®
HVAC Drive FC 102
192 Danfoss A/S © 11/2017 All rights reserved. MG16C302
1010