VLT
®
HVAC Drive FC 102
P800 P1000
Normal overload NO NO
(Normal overload=110% current during 60 s)
Typical shaft output at 400 V [kW] 800 1000
Typical shaft output at 460 V [hp] 1200 1350
Typical shaft output at 480 V [kW] 1000 1100
Enclosure size F12/F13 F12/F13
Output current (3-phase)
Continuous (at 400 V) [A] 1460 1720
Intermittent (60 s overload) (at 400 V) [A] 1606 1892
Continuous (at 460/480 V) [A] 1380 1530
Intermittent (60 s overload)(at 460/480 V) [A] 1518 1683
Continuous kVA (at 400 V) [kVA] 1012 1192
Continuous kVA (at 460 V) [kVA] 1100 1219
Continuous kVA (at 480 V) [kVA] 1195 1325
Maximum input current
Continuous (at 400 V) [A] 1407 1658
Continuous (at 460/480 V) [A] 1330 1474
Maximum number and size of cables per phase
- Motor [mm
2
(AWG)]
12x150 (12x300
mcm)
12x150 (12x300
mcm)
- Mains [mm
2
(AWG)]
6x120 (6x250 mcm) 6x120 (6x250 mcm)
- Brake [mm
2
(AWG)]
6x185 (6x350 mcm) 6x185 (6x350 mcm)
Maximum external mains fuses [A]
1)
1500 1500
Estimated power loss at 400 V [W]
2), 3)
18084 20358
Estimated power loss at 460 V [W]
2), 3)
17137 17752
Maximum added losses A1 RFI, circuit breaker or disconnect, and contactor [W], (F4 only) 2280 2541
Maximum panel options losses [W] 400 400
Eciency
3)
0.98 0.98
Output frequency [Hz] 0–590 0–590
Control card overtemperature trip [°C (°F)]
85 (185) 85 (185)
Table 7.6 Electrical Data for Enclosures F12/F13, Mains Supply 6x380–480 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor eciency (IE/IE3 border line). Lower eciency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
eciency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.5 ft) shielded motor cables at rated load and rated frequency. Eciency measured at nominal current. For energy
eciency class, see chapter 10.12 Eciency. For part load losses, see drives.danfoss.com/knowledge-center/energy-eciency-directive/#/.
Specications Design Guide
MG16C302 Danfoss A/S © 11/2017 All rights reserved. 53
7 7