4.2.7 Ordering Numbers: Brake Resistors
NOTE!
When/where two resistors are listed in the tables - order two resistors.
Ordering Numbers: Brake Resistors
Line power 200–240 V AC (T2-LP+MP)
VLT AQUA Drive
Selected resistor
Standard IP 20
Flatpack IP65
for horizontal conveyors
Max.
brake tor-
que with
R
rec
Duty Cycle 10% Duty Cycle 40%
Size: P
motor
R
min
R
br,nom
R
rec
P
br avg
Order no. Period R
rec
P
br avg
Order no. Period R
rec
per
item
Duty cycle Order no.
[kW] [] [] [] [kW] 175Uxxxx [s] [] [kW] 175Uxxxx [s] [/w] % 175Uxxxx %
PK25 0.25 380 679 425 0.095 1841 120 425 0.43 1941 120 430/100 40 1002 110 (110)
PK37 0.37 380 459 425 0.095 1841 120 425 0.43 1941 120 430/100 40 1002 110 (110)
PK55 0.55 275 307 310 0.25 1842 120 310 0.80 1942 120 330/100 27 1003 109 (110)
PK55 0.55 275 307 310 0.25 1842 120 310 0.80 1942 120 310/200 55 0984 109 (110)
PK75 0.75 188 224 210 0.285 1843 120 210 1.35 1943 120 220/100 20 1004 110 (110)
PK75 0.75 188 224 210 0.285 1843 120 210 1.35 1943 120 210/200 37 0987 110 (110)
P1K1 1.1 130 152 145 0.065 1820 120 145 0.26 1920 120 150/100 14 1005 110 (110)
P1K1 1.1 130 152 145 0.065 1820 120 145 0.26 1920 120 150/200 27 0989 110 (110)
P1K5 1.5 81 110 90 0.095 1821 120 90 0.43 1921 120 100/100 10 1006 110 (110)
P1K5 1.5 81 110 90 0.095 1821 120 90 0.43 1921 120 100/200 19 0991 110 (110)
P2K2 2.2 58 74.2 65 0.25 1822 120 65 0.80 1922 120 72/200 14 0992 110 (110)
P3K0 3 45 53.8 50 0.285 1823 120 50 1.0 1923 120 50/200 10 0993 110 (110)
P3K7 3.7 31.5 43.1 35 0.43 1824 120 35 1.35 1924 120 35/200 7 0994 110 (110)
P3K7 3.7 31.5 43.1 35 0.43 1824 120 35 1.35 1924 120 72/200 14 2X0992 110 (110)
P5K5 5.5 22.5 28.7 25 0.8 1825 120 25 3.0 1925 120 60/200 11 2x0996 110 (110)
P7K5 7.5 18 20.8 20 2.0 1826 120 20 - - - - - - 110 (110)
P11K 11 12.6 14.0 15 2.0 1827 120 15 - - - - - - 103 (110)
P15K 15 9 10.2 10 2.8 1828 120 10 - - - - - - 110 (110)
P18K 18.5 6.3 8.2 7 4 1829 120 7 - - - - - - 110 (110)
P22K 22 5.4 6.9 6 4.8 1830 120 6 - - - - - - 110 (110)
P30K 30 4.2 5.0 4.7 6 1954 300 4.7 - - - - - - 110 (110)
P37K 37 2.9 4.0 3.3 8 1955 300 3.3 - - - - - - 110 (110)
P45K 45 2.4 3.3 2.7 10 1956 300 2.7 - - - - - - 110 (110)
4 How to Order VLT
®
AQUA Drive Design Guide
4-16
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
4

Table of Contents

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled