3
/h
Distribution Valve regulation Adjustable frequency drive control
% Hours Power Consumption Power Consumption
A
1
- B
1
kWh A
1
- C
1
kWh
350 5 438 42.5 18.615 42.5 18.615
300 15 1314 38.5 50.589 29.0 38.106
250 20 1752 35.0 61.320 18.5 32.412
200 20 1752 31.5 55.188 11.5 20.148
150 20 1752 28.0 49.056 6.5 11.388
100 20 1752 23.0 40.296 3.5 s
Σ 100 8760 275.064 26.801
2.7.5 Better Control
If an adjustable frequency drive is used for controlling the flow or pressure of a system, improved control is obtained.
An adjustable frequency drive can vary the speed of the fan or pump, thereby obtaining variable control of flow and pressure.
Furthermore, an adjustable frequency drive can quickly adapt the speed of the fan or pump to new flow or pressure conditions in the system.
Simple control of process (flow, level or pressure) utilizing the built-in PID control.
2.7.6 Cos φ Compensation
Generally speaking, an adjustable frequency drive with a cos φ of 1 provides power factor correction for the cos φ of the motor, which means that there
is no need to make allowance for the cos φ of the motor when sizing the power factor correction unit.
VLT
®
AQUA Drive Design Guide 2 Introduction to the VLT AQUA Drive
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
2-9
2

Table of Contents

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled