Line Power Supply 1 x 200–240 V AC - Normal overload 110% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW]
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3.0
P3K7
3.7
P5K5
5.5
P7K5
7.5
P15K0
15
P22K0
22
Typical Shaft Output [HP] at 240 V 1.5 2.0 2.9 4.0 4.9 7.5 10 20 30
IP 20 / Chassis A3 - - - - - - - -
IP 21 / NEMA 1 - B1B1B1B1B1 B2 C1C2
IP 55 / NEMA 12 A5 B1 B1 B1 B1 B1 B2 C1 C2
IP 66 A5 B1 B1 B1 B1 B1 B2 C1 C2
Output current
Continuous
(3 x 200–240 V) [A]
6.6 7.5 10.6 12.5 16.7 24.2 30.8 59.4 88
Intermittent
(3 x 200–240 V) [A]
7.3 8.3 11.7 13.8 18.4 26.6 33.4 65.3 96.8
Continuous kVA
(208 V AC) [kVA]
5.00 6.40 12.27 18.30
Max. cable size:
(line power, motor, brake)
[[mm
2
/ AWG]
2)
0.2-4 / 4-10 10/7 35/2 50/1/0 95/4/0
Max. input current
Continuous
(1 x 200–240 V) [A]
12.5 15 20.5 24 32 46 59 111 172
Intermittent
(1 x 200–240 V) [A]
13.8 16.5 22.6 26.4 35.2 50.6 64.9 122.1 189.2
Max. pre-fuses
1)
[A]
20 30 40 40 60 80 100 150 200
Environment
Estimated power loss
at rated max. load [W]
4)
44 30 44 60 74 110 150 300 440
Weight enclosure IP 20 [kg] 4.9 - - - - - - - -
Weight enclosure IP 21 [kg] - 23 23 23 23 23 27 45 65
Weight enclosure IP 55 [kg] - 23 23 23 23 23 27 45 65
Weight enclosure IP 66 [kg] - 23 23 23 23 23 27 45 65
Efficiency
3)
0.968 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
3.1.1 Line Power Supply 1 x 200–240 V AC
3 VLT AQUA Selection VLT
®
AQUA Drive Design Guide
3-2
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
3

Table of Contents

Other manuals for Danfoss vlt aqua

Related product manuals