EasyManua.ls Logo

Danfoss vlt aqua - Page 47

Danfoss vlt aqua
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Normal overload 110% for 1 minute
IP 20 / NEMA Chassis A2 A2 A2 A2 A2 A2 A2 A3 A3
IP 21 / NEMA 1 A2 A2 A2 A2 A2 A2 A2 A3 A3
IP 55 / NEMA 12 A5 A5 A5 A5 A5 A5 A5 A5 A5
IP 66 A5 A5 A5 A5 A5 A5 A5 A5 A5
Line power supply 200–240 V AC
Adjustable frequency drive
Typical Shaft Output [kW]
PK25
0.25
PK37
0.37
PK55
0.55
PK75
0.75
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P3K7
3.7
Typical Shaft Output [HP] at 208 V 0.25 0.37 0.55 0.75 1.5 2.0 2.9 4.0 4.9
Output current
Continuous
(3 x 200–240 V) [A]
1.8 2.4 3.5 4.6 6.6 7.5 10.6 12.5 16.7
Intermittent
(3 x 200–240 V) [A]
1.98 2.64 3.85 5.06 7.26 8.3 11.7 13.8 18.4
Continuous
kVA (208 V AC) [kVA]
0.65 0.86 1.26 1.66 2.38 2.70 3.82 4.50 6.00
Max. cable size:
(line power, motor, brake)
[mm
2
/AWG]
2)
0.00031–0.0062 in
2
[0.2–4 mm
2
] / 4–10 AWG
Max. input current
Continuous
(3 x 200–240 V) [A]
1.6 2.2 3.2 4.1 5.9 6.8 9.5 11.3 15.0
Intermittent
(3 x 200–240 V) [A]
1.7 2.42 3.52 4.51 6.5 7.5 10.5 12.4 16.5
Max. pre-fuses
1)
[A]
10 10 10 10 20 20 20 32 32
Environment
Estimated power loss
at rated max. load [W]
4)
21 29 42 54 63 82 116 155 185
Weight enclosure IP20 [kg] 4.9 4.9 4.9 4.9 4.9 4.9 4.9 6.6 6.6
Weight enclosure IP21 [kg] 5.5 5.5 5.5 5.5 5.5 5.5 5.5 7.5 7.5
Weight enclosure IP55 [kg] 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5
Weight enclosure IP66 [kg] 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5
Efficiency
3)
0.94 0.94 0.95 0.95 0.96 0.96 0.96 0.96 0.96
3.1.2 Line power Supply 3 x 200–240 V AC
VLT
®
AQUA Drive Design Guide 3 VLT AQUA Selection
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
3-3
3

Table of Contents