Line power supply 3 x 200–240 V AC - Normal overload 110% for 1 minute
IP 20 / NEMA Chassis
(B3+4 and C3+4 may be converted to IP21 using a conversion kit (Please contact Danfoss)
B3 B3 B3 B4 B4 C3 C3 C4 C4
IP 21 / NEMA 1 B1 B1 B1 B2 C1 C1 C1 C2 C2
IP 55 / NEMA 12 B1 B1 B1 B2 C1 C1 C1 C2 C2
IP 66 B1 B1 B1 B2 C1 C1 C1 C2 C2
Adjustable frequency drive
Typical Shaft Output [kW]
P5K5
5.5
P7K5
7.5
P11K
11
P15K
15
P18K
18.5
P22K
22
P30K
30
P37K
37
P45K
45
Typical Shaft Output [HP] at 208 V 7.5101520253040 50 60
Output current
Continuous
(3 x 200–240 V) [A]
24.2 30.8 46.2 59.4 74.8 88.0 115 143 170
Intermittent
(3 x 200–240 V) [A]
26.6 33.9 50.8 65.3 82.3 96.8 127 157 187
Continuous
kVA (208 V AC) [kVA]
8.7 11.1 16.6 21.4 26.9 31.7 41.4 51.5 61.2
Max. cable size:
(line power, motor, brake)
[mm
2
/AWG]
2)
10/7 35/2 50/1/0 95/4/0
120/250
MCM
Max. input current
Continuous
(3 x 200–240 V) [A]
22.0 28.0 42.0 54.0 68.0 80.0 104.0 130.0 154.0
Intermittent
(3 x 200–240 V) [A]
24.2 30.8 46.2 59.4 74.8 88.0 114.0 143.0 169.0
Max. pre-fuses
1)
[A]
63 63 63 80 125 125 160 200 250
Environment:
Estimated power loss
at rated max. load [W]
4)
269 310 447 602 737 845 1140 1353 1636
Weight enclosure IP20 [kg] 12 12 12 23.5 23.5 35 35 50 50
Weight enclosure IP21 [kg] 23 23 23 27 45 45 65 65 65
Weight enclosure IP55 [kg] 23 23 23 27 45 45 65 65 65
Weight enclosure IP66 [kg] 23 23 23 27 45 45 65 65 65
Efficiency
3)
0.96 0.96 0.96 0.96 0.96 0.97 0.97 0.97 0.97
3 VLT AQUA Selection VLT
®