Line Power Supply 1x 380 V AC - Normal overload 110% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW]
P7K5
7.5
P11K
11
P18K
18.5
P37K
37
Typical Shaft Output [HP] at 460 V 10 15 25 50
IP 21 / NEMA 1 B1 B2 C1 C2
IP 55 / NEMA 12 B1 B2 C1 C2
IP 66 B1 B2 C1 C2
Output current
Continuous (3 x 380–440 V) [A] 16 24 37.5 73
Intermittent (3 x 380–440 V) [A] 17.6 26.4 41.2 80.3
Continuous (3 x 441–480 V) [A] 14.5 21 34 65
Intermittent (3 x 441–480 V) [A] 15.4 23.1 37.4 71.5
Continuous kVA (400 V AC) [kVA] 11.0 16.6 26 50.6
Continuous kVA (460 V AC) [kVA] 11.6 16.7 27.1 51.8
Max. cable size:
(line power, motor, brake)
[[mm
2
/ AWG]
2)
10/7 35/2 50/1/0 120/4/0
Max. input current
Continuous (1 x 380–440 V) [A] 33 48 78 151
Intermittent (1 x 380–440 V) [A] 36 53 85.8 166
Continuous (1 x 441–480 V) [A] 30 41 72 135
Intermittent (1 x 441–480 V) [A] 33 46 79.2 148
Max. pre-fuses
1)
[A]
63 80 160 250
Environment
Estimated power loss
at rated max. load [W]
4)
300 440 740 1480
Weight enclosure IP 21 [kg] 23 27 45 65
Weight enclosure IP 55 [kg] 23 27 45 65
Weight enclosure IP 66 [kg] 23 27 45 65
Efficiency
3)
0.96 0.96 0.96 0.96
3.1.3 Line Power Supply 1 x 380–480 V AC
VLT
®
AQUA Drive Design Guide 3 VLT AQUA Selection
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
3-5