Normal overload 110% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW] at 400 V
P110
110
P132
132
P160
160
P200
200
P250
250
315
P400
400
P450
450
P500
500
P560
560
P630
630
P710
710
P800
800
P1M0
1000
Typical Shaft Output [HP] at 460V 150 200 250 300 350 450 550 600 650 750 900 1000 1200 1350
IP 00 D3 D3 D4 D4 D4 E2 E2 E2 F1/F3 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4
IP 21 / Nema 1 D1 D1 D2 D2 D2 E1 E1 E1 F1/F3 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4
IP 54 / Nema 12 D1 D1 D2 D2 D2 E1 E1 E1 F1/F3 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4
Output current
Continuous (3 x 380–440 V) [A] 212 260 315 395 480 600 745 800 880 990 1120 1260 1460 1720
Intermittent (3 x 380–440 V) [A] 233 286 347 435 528 660 820 880 968 1089 1232 1386 1606 1892
Continuous (3 x 441–480 V) [A] 190 240 302 361 443 540 678 730 780 890 1050 1160 1380 1530
Intermittent (3 x 441–480 V) [A] 209 264 332 397 487 594 746 803 858 979 1155 1276 1518 1683
Continuous kVA (400 V AC) [kVA] 147 180 218 274 333 416 516 554 610 686 776 873 1012 1192
Continuous kVA (460 V AC) [kVA] 151 191 241 288 353 430 540 582 621 709 837 924 1100 1219
Max. cable size:
(motor,) [mm
2
/ AWG
2)
]
2x70
2x2/0
2x185
2x300 mcm
4x240
4x500 mcm
8x150
8x300 mcm
12x150
12x300 mcm
(line power) [mm
2
/ AWG
2)
]
2x70
2x2/0
2x185
2x300 mcm
4x240
4x500 mcm
8x240
8x500 mcm
(loadsharing) [mm
2
/ AWG
2)
]
2x70
2x2/0
2x185
2x300 mcm
4x240
4x500 mcm
4x120
4x250 mcm
(brake) [mm
2
/ AWG
2)
]
2x70
2x2/0
2x185
2x300 mcm
2x185
2x350 mcm
4x185
4x350 mcm
6x185
6x350 mcm
3 VLT AQUA Selection VLT
®
AQUA Drive Design Guide
3-8
MG.20.N5.22 - VLT
®