Normal overload 110% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW] at 400 V
P110
110
P132
132
P160
160
P200
200
P250
250
315
P400
400
P450
450
P500
500
P560
560
P630
630
P710
710
P800
800
P1M0
1000
Typical Shaft Output [HP] at 460V 150 200 250 300 350 450 550 600 650 750 900 1000 1200 1350
IP 00 D3 D3 D4 D4 D4 E2 E2 E2 F1/F3 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4
IP 21 / Nema 1 D1 D1 D2 D2 D2 E1 E1 E1 F1/F3 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4
IP 54 / Nema 12 D1 D1 D2 D2 D2 E1 E1 E1 F1/F3 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4
Max. input current
Continuous (3 x 380–440 V) [A] 204 251 304 381 463 590 733 787 857 964 1090 1227 1422 1675
Continuous (3 x 441–480 V) [A] 183 231 291 348 427 531 667 718 759 867 1022 1129 1344 1490
Max. pre-fuses
1)
[A]
300 350 400 500 630 700 900 900 1600 1600 2000 2000 2500 2500
Environment:
Estimated power loss at 400 V AC
at rated max. load [W]
4)
3234 3782 4213 5119 5893 6790 8879 9670 10647 12338 13201 15436 18084 20358
Estimated power loss at 460 V AC
at rated max. load [W]
4)
2947 3665 4063 4652 5634 6082 8089 8803 9414 11006 12353 14041 17137 17752
Weight enclosure IP00 [kg] 82 91 112 123 138 221 236 277 - - - - - -
Weight enclosure IP 21 [kg] 96 104 125 136 151 263 272 313 1004 1004 1004 1004 1246 1246
Weight enclosure IP 54 [kg] 96 104 125 136 151 263 272 313 1299 1299 1299 1299 1541 1541
Efficiency
3)
0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
1)
For type of fuse see section
Fuses
2)
American Wire Gauge
3)
Measured using 16 ft [5 m] shielded motor cables at rated load and rated frequency
4)
The typical power loss is at normal load conditions and expected to be within +/-15% (tolerance relates to variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiency motors will also add to the power loss in the adjustable frequency drive and vice versa.
If the switching frequency is raised from nominal, the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 W to the losses. (Though typically only 4 W extra for a fully loaded control card or options for
slot A or slot B, each).
Although measurements are made with state-of-the-art equipment, some measurement inaccuracy must be allowed for (+/-5%).