Control card performance:
Scan interval : 5 ms
Control card, USB serial communication:
USB standard 1.1 (Full speed)
USB plug USB type B “device” plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is
not galvanically isolated from protection ground. Only use an isolated laptop/PC as the connection to the USB
connector on an VLT AQUA Drive or an isolated USB cable/drive.
3 VLT AQUA Selection VLT
®
AQUA Drive Design Guide