3.6.7 Relay Option MCB 105
The MCB 105 option includes 3 pieces of SPDT contacts and must be fitted into option slot B.
Electrical Data:
Max terminal load (AC-1)
1)
(Resistive load) 240 V AC 2A
Max terminal load (AC-15)
1)
(Inductive load @ cosφ 0.4) 240 V AC 0.2 A
Max terminal load (DC-1)
1)
(Resistive load) 24 V DC 1 A
Max terminal load (DC-13)
1)
(Inductive load) 24 V DC 0.1 A
Min terminal load (DC) 5 V 10 mA
Max switching rate at rated load/min load 6 min
-1
/20 sec
-1
1) IEC 947 part 4 and 5
When the relay option kit is ordered separately, the kit includes:
Relay Module MCB 105
Extended LCP frame and enlarged terminal cover
Label for covering access to switches S201, S202 and S801
Cable strips for fastening cables to relay module
A2-A3-B3 A5-B1-B2-B4-C1-C2-C3-C4
1)
IMPORTANT! The label MUST be placed on the LCP frame as shown (UL approved).
3 VLT AQUA Selection VLT
®
AQUA Drive Design Guide
3-34
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
3

Table of Contents

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals