Control characteristics:
Resolution of output frequency at 0–1000 Hz : +/- 0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, 33) : 2 ms
Speed control range (open-loop) 1:100 of synchronous speed
Speed accuracy (open-loop) 30–4000 rpm: Maximum error of ±8 rpm
All control characteristics are based on a 4-pole asynchronous motor
Surroundings:
Enclosure, frame size D and E IP 21, IP 54 (hybrid)
Enclosure, frame size F IP 21, IP 54 (hybrid)
Vibration test 0.7 g
Relative humidity 5–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class kD
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating max. 131°F [55 °C]
1)
- with full output power, typical EFF2 motors max. 122°F [50°C]
1)
- at full continuous FC output current max. 113°F [45°C]
1)
1)
For more information on derating see the Design Guide, section on Special Conditions.
Minimum ambient temperature during full-scale operation 32°F [0°C]
Minimum ambient temperature at reduced performance 14°F [- 10 °C]
Temperature during storage/transport -13°–+149°/158°F [-25°–+65°/70°°C]
Maximum altitude above sea level without derating 3280 ft [1000 m]
Maximum altitude above sea level with derating 9842 ft [3000 m]
Derating for high altitude, see section on special conditions
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions!
Control card performance:
Scan interval : 5 ms
Control card, USB serial communication:
USB standard 1.1 (Full speed)
USB plug USB type B “device” plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is
not galvanically isolated from protection ground. Use only isolated laptop/PC as connection to the USB connector
on the adjustable frequency drive or an isolated USB cable/drive.
Protection and Features:
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips if the temperature reaches a predefined level. An
overload temperature cannot be reset until the temperature of the heatsink is below the values stated in the tables on the following pages
(guideline - these temperatures may vary for different power sizes, frame sizes, enclosure ratings, etc.).
The adjustable frequency drive is protected against short-circuits on motor terminals U, V, W.
If a line phase is missing, the adjustable frequency drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips if the intermediate circuit voltage is too low or
too high.
The adjustable frequency drive is protected against ground faults on motor terminals U, V, W.
8 General Specifications
VLT AQUA Low Harmonic Drive Instruction
Manual
8-4