7.5 Examples
7.5.1 Writing a Parameter Value
Change par. 4-14 
Motor Speed High Limit [Hz]
 to 100 Hz.
Write the data in EEPROM.
PKE = E19E Hex - Write single word in par. 4-14 
Motor Speed High Limit
[Hz]
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 03E8 Hex - Data value 1000, corresponding to 100 Hz, see
Conversion.
The message will look like this:
Note: Par. 4-14 
Motor Speed High Limit [Hz]
 is a single word, and the
parameter command for write in EEPROM is “E”. Parameter number 4-14
is 19E in hexadecimal.
The response from the slave to the master will be:
 
7.5.2 Reading a Parameter Value
Read the value in par. 3-41 
Ramp 1 Ramp-up Time
PKE = 1155 Hex - Read parameter value in par. 3-41 
Ramp 1 Ramp-up
Time
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 0000 Hex
If the value in par. 3-41 
Ramp 1 Ramp-up Time
 is 10 s, the response from
the slave to the master will be:
3E8 Hex corresponds to 1000 decimal. The conversion index for par. 3-41 
Ramp 1 Ramp-up Time
 is -2, i.e., 0.01.
par. 3-41 
Ramp 1 Ramp-up Time
 is of the type 
Unsigned 32
.
VLT AQUA Low Harmonic Drive Instruction
Manual
7 RS-485 Installation and Set-up
MG.20.T1.22 - VLT
®