Power size [kW (hp)] Cable [m (ft)] Mains voltage [V]
Rise time [µs]
Peak voltage [V]
dU/dt [V/µs]
55–132 (60–150) 30 (98) 690
150 (492) 690 1.03 2045 1590
300 (984) 690 1.41 2132 1217
160–315 (200–350) 30 (98) 690
150 (492) 690 1.00 2022 1617
300 (984) 690 1.15 2097 1459
Table 10.30 IEC dU/dt Test Results for D1h–D8h with Shielded Cables and No Output Filter, 525–690 V
10.13.2 dU/dt Test Results for Enclosures E1h–E4h
Test results for 380–500 V
Power size [kW (hp)] Cable [m (ft)] Mains voltage [V]
Rise time [µs]
Peak voltage [V]
dU/dt [V/µs]
315–400 (450–550) 5 (16) 460 0.23 1038 2372
30 (98) 460 0.72 1061 644
150 (492) 460 0.46 1142 1160
300 (984) 460 1.84 1244 283
450–500 (600–650) 5 (16) 460 0.42 1042 1295
30 (98) 460 0.57 1200 820
150 (492) 460 0.63 1110 844
300 (984) 460 2.21 1175 239
Table 10.31 NEMA dU/dt Test Results for E1h–E4h with Unshielded Cables and No Output Filter, 380–500 V
Power size [kW (hp)] Cable [m (ft)] Mains voltage [V]
Rise time [µs]
Peak voltage [V]
dU/dt [V/µs]
315–400 (450–550) 5 (16) 460 0.33 1038 2556
30 (98) 460 1.27 1061 668
150 (492) 460 0.84 1142 1094
300 (984) 460 2.25 1244 443
450–500 (600–650) 5 (16) 460 0.53 1042 1569
30 (98) 460 1.22 1200 1436
150 (492) 460 0.90 1110 993
300 (984) 460 2.29 1175 411
Table 10.32 IEC dU/dt Test Results for E1h–E4h with Unshielded Cables and No Output Filter, 380–500 V
Power size [kW (hp)] Cable [m (ft)] Mains voltage [V]
Rise time [µs]
Peak voltage [V]
dU/dt [V/µs]
315–400 (450–550) 5 (16) 460 0.17 1017 3176
30 (98) 460
150 (492) 460 0.41 1268 1311
450–500 (600–650) 5 (16) 460 0.17 1042 3126
30 (98) 460
150 (492) 460 0.22 1233 2356
Table 10.33 NEMA dU/dt Test Results for E1h–E4h with Shielded Cables and No Output Filter, 380–500 V
Power size [kW (hp)] Cable [m (ft)] Mains voltage [V]
Rise time [µs]
Peak voltage [V]
dU/dt [V/µs]
315–400 (450–550) 5 (16) 460 0.26 1017 3128
30 (98) 460
150 (492) 460 0.70 1268 1448
450–500 (600–650) 5 (16) 460 0.27 1042 3132
30 (98) 460
150 (492) 460 0.52 1233 1897
Table 10.34 IEC dU/dt Test Results for E1h–E4h with Shielded Cables and No Output Filter, 380–500 V