Enclosure size E1h E2h E3h E4h
Power rating
1)
Output at 690 V (kW) 355–560 630–710 355–560 630–710
Output at 575 V (hp) 400–600 650–750 400–600 650–750
Protection rating
IP IP21/54 IP21/54
IP20
2)
IP20
2)
UL type Type 1/12 Type 1/12 Chassis Chassis
Hardware options
3)
Stainless steel back channel O O O O
Mains shielding O O
Space heater O O
RFI lter (Class A1)
Safe torque o S S S S
No LCP O O O O
Graphical LCP O O O O
Fuses S S O O
Heat sink access O O O O
Brake chopper O O O O
Regen terminals O O O O
Load share terminals O O
Fuses + load share O O
Disconnect O O
Circuit breakers
Contactors
24 V DC supply (SMPS, 5 A)
Dimensions
Height, mm (in) 2043 (80.4) 2043 (80.4) 1578 (62.1) 1578 (62.1)
Width, mm (in) 602 (23.7) 698 (27.5) 506 (19.9) 604 (23.9)
Depth, mm (in) 513 (20.2) 513 (20.2) 482 (19.0) 482 (19.0)
Weight, kg (lb) 295 (650) 318 (700) 272 (600) 295 (650)
Table 4.6 E1h–E4h Drives, 525–690 V
1) All power ratings are taken at high overload. Output is measured at 690 V (kW) and 575 V (hp).
2) If the enclosure is congured with load share or regen terminals, then the protection rating is IP00, otherwise the protection rating is IP20.
3) S = standard, O = optional, and a dash indicates that the option is unavailable.