9-70 Edit Set-up
Option: Function:
Select the set-up to be edited.
[0] Factory setup Uses default data. This option can be used as a data source to return the other set-ups to a known state.
[1]
*
Setup 1 Edits Set-up 1.
[2] Setup 2 Edits Set-up 2.
[3] Setup 3 Edits Set-up 3.
[4] Setup 4 Edits Set-up 4.
[9] Active setup Follows the active set-up selected in par. 0-10.
This parameter is unique to LCP and fieldbuses. See also par. 0-11
Edit set-up
.
9-71 Save Data Values
Option: Function:
Parameter values changed via Profibus are not automatically stored in non-volatile memory. Use this parameter
to activate a function that stores parameter values in the EEPROM non-volatile memory, so changed parameter
values will be retained at power-down.
[0]
*
Off Deactivates the non-volatile storage function.
[1] Store edit setup Stores all parameter values in the set-up selected in par. 9-70 in the non-volatile memory. The selection returns
to Off [0] when all values have been stored.
[2] Store all set-ups Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all
parameter values have been stored.
9-72 Drive Reset
Option: Function:
[0]
*
No action
[1] Power-on reset Resets frequency converter upon power-up, as for power-cycle.
[3] Comm. option reset Resets the Profibus option only, useful after changing certain settings in parameter group 9-**, e.g. par. 9-18.
When reset, the frequency converter disappears from the fieldbus, which may cause a communication error
from the master.
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
0
*
[0 - 115]
This parameter displays a list of all the defined frequency converter parameters available for Profibus.
9-81 Defined Parameters (2)
Array [116]
No LCP access
Read only
0
*
[0 - 115]
This parameter displays a list of all the defined frequency converter parameters available for Profibus.
3. Parameter Description VLT
®
HVAC Drive Programming Guide
104
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals