[0] Disable Disables process control via Profibus, and enables process control via standard fieldbus or Profibus Master class
2.
[1]
*
Enable cyclic master Enables process control via Profibus Master Class 1, and disables process control via standard fieldbus or Profibus
Master class 2.
9-53 Profibus Warning Word
Option: Function:
This parameter displays Profibus communication warnings. Please refer to the
Profibus Operating Instructions
for further information.
Read only
Bit:
Meaning:
0 Connection with DP-master is not ok
1Not used
2 FDL (Field-bus Data link Layer) is not ok
3 Clear data command received
4 Actual value is not updated
5 Baudrate search
6 PROFIBUS ASIC is not transmitting
7 Initializing of PROFIBUS is not ok
8 Frequency converter is tripped
9 Internal CAN error
10 Wrong configuration data from PLC
11 Wrong ID sent by PLC
12 Internal error occured
13 Not configured
14 Timeout active
15 Warning 34 active
9-63 Actual Baud Rate
Option: Function:
This parameter displays the actual Profibus baud rate. The Profibus Master automatically sets the baud rate.
Read only
[0] 9.6 kbit/s
[1] 19.2 kbit/s
[2] 93.75 kbit/s
[3] 187.5 kbit/s
[4] 500 kbit/s
[6] 1500 kbit/s
[7] 3000 kbit/s
[8] 6000 kbit/s
[9] 12000 kbit/s
[10] 31.25 kbit/s
[11] 45.45 kbit/s
[255] No baud rate found
9-65 Profile Number
Range: Function:
Read only
0
*
[0 - 0]
This parameter contains the profile identification. Byte 1 contains the profile number and byte 2 the version
number of the profile.
NB!
This parameter is not visible via LCP.
VLT
®
HVAC Drive Programming Guide 3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
103