Data transfer from LCP to frequency converter:
1. Go to par. 0-50
LCP Copy
2. Press the [OK] key
3. Select “All from LCP”
4. Press the [OK] key
The parameter settings stored in the LCP are now transferred to the frequency converter indicated by the progress bar. When 100% is reached, press
[OK].
NB!
Stop the motor before performing this operation.
2.1.4. Parameter Set-Up
The frequency converter can be used for practically all assignments, thus offering a significant number of parameters. The series offers a choice between
two programming modes - a Quick Menu mode and a Main Menu mode.
The latter provides access to all parameters. The former takes the user through a few parameters making it possible to program the majority of VLT
HVAC Drive applications.
Regardless of the mode of programming, you can change a parameter both in the Quick Menu mode and in the Main Menu mode.
2.1.5. Quick Menu Mode
Parameter Data
The graphical display (GLCP) provides access to all parameters listed under the Quick Menus. The numeric display (NLCP) only provides access to the
Quick Setup parameters. To set parameters using the [Quick Menu] button - enter or change parameter data or settings in accordance with the following
procedure:
1. Press Quick Menu button
2.
Use the [
] and [
] buttons to find the parameter you want to change
3. Press [OK]
4.
Use [
] and [
] buttons to select the correct parameter setting
5. Press [OK]
6.
To move to a different digit within a parameter setting, use the [
] and [
] buttons
7. Highlighted area indicates digit selected for change
8. Press [Cancel] button to disregard change, or press [OK] to accept change and enter the new setting
Example of Changing Parameter Data
Assume parameter 22-60
Broken Belt Function
is set to [Off]. However, you want to monitor the fan-belt condition - non- broken or broken - according
to the folowing procedure:
1. Press Quick Menu key
2.
Choose Function Setups with the [
] button
3. Press [OK]
4.
Choose Application Settings with the [
] button
5. Press [OK]
6. Press [OK] again for Fan Functions
7. Choose Broken Belt Function by pressing [OK]
8.
With [
] button, choose [2] Trip
The frequency converter will now trip if a broken fan-belt is detected.
VLT
®
HVAC Drive Programming Guide 2. How to Programme
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
13
2

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals