EasyManuals Logo
Home>Danfoss>DC Drives>VLT FC 100 Series

Danfoss VLT FC 100 Series Programming Guide

Danfoss VLT FC 100 Series
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #126 background imageLoading...
Page #126 background image
Illustration 3.3: Controlled Ramp-down, longer mains failure. Ramping down as long as the energy in the system allows for it, then the motor is coasted.
Illustration 3.4: Kinetic Back-up, short mains failure. Ride through as long as the energy in the system allows for it.
Illustration 3.5: Kinetic Back-up, longer mains failure. The motor is coasted as soon as the energy in the system is too low.
14-11 Mains Voltage at Mains Fault
Range: Function:
342 V
*
[150 - 600 V]
This parameter defines the threshold voltage at which the selected function in par. 14-10 should be activated.
14-12 Function at Mains Imbalance
Option: Function:
Operation under severe main imbalance conditions reduces the lifetime of the motor. Conditions are considered
severe if the motor is operated continuously near nominal load (e.g. a pump or fan running near full speed).
3. Parameter Description VLT
®
HVAC Drive Programming Guide
126
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals