14-42 Minimum AEO Frequency
Range: Function:
10Hz
*
[5 - 40 Hz]
Enter the minimum frequency at which the Automatic Energy Optimisation (AEO) is to be active.
14-43 Motor Cosphi
Range: Function:
0.66
*
[0.40 - 0.95]
The Cos(phi) setpoint is automatically set for optimum AEO performance during AMA. This parameter should
normally not be altered. However in some situations it may be necessary to enter a new value to fine-tune.
3.14.7. Environment, 14-5*
These parameters help the frequency converter to operate under special environmental conditions.
14-50 RFI 1
Option: Function:
[0] Off Select
Off
[0] only if the frequency converter is fed by an isolated mains source, i.e. from a special IT mains
source.
In this mode, the internal RFI filter capacitors between chassis and the mains RFI filter circuit are cut-out to
avoid damage of the intermediate circuit and to reduce the ground capacity currents according to IEC 61800-3.
[1]
*
On Select
On
[1] to ensure that the frequency converter complies with EMC standards.
14-52 Fan Control
Option: Function:
Select the minimum speed of the main fan.
[0]
*
Auto Select Auto [0] to run the fan only when the internal temperature of the frequency converter is in the range
+35 °C to approximately +55°C. The fan will run at low speed at +35C and at full speed at approximately +55°
C.
[1] On 50%
[2]
[3]
On 75%
On 100%
14-53 Fan Monitor
Option: Function:
Select which reaction the frequency converter should take in case a fan fault is detected.
[0] Disabled
[1]
*
Warning
[2] Trip
14-55 Output Filter
Option: Function:
Select the type of output filter connected. This parameter cannot be adjusted while motor is running.
[0]
*
No filter
[1] Sine-Wave Filter
3.14.8. Auto Derate, 14-6*
This group contains parameters for derating the frequency converter in case of high temperature.
3. Parameter Description VLT
®
HVAC Drive Programming Guide
130
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals