Par. No. # Parameter description Default value
(SR = Size related)
4-set-up FC 302
only
Change during op-
eration
Conver-
sion index
Type
2-0* DC-Brake
2-00 DC Hold/Preheat Current 50 % All set-ups TRUE 0 Uint8
2-01 DC Brake Current 50 % All set-ups TRUE 0 Uint16
2-02 DC Braking Time 10.0 s All set-ups TRUE -1 Uint16
2-03 DC Brake Cut In Speed [RPM] SR All set-ups TRUE 67 Uint16
2-04
DC Brake Cut In Speed [Hz] SR All set-ups TRUE -1 Uint16
2-1* Brake Energy Funct.
2-10 Brake Function [0] Off All set-ups TRUE - Uint8
2-11 Brake Resistor (ohm) SR All set-ups TRUE 0 Uint16
2-12 Brake Power Limit (kW) SR All set-ups TRUE 0 Uint32
2-13 Brake Power Monitoring [0] Off All set-ups TRUE - Uint8
2-15 Brake Check [0] Off All set-ups TRUE - Uint8
2-16 AC brake Max. Current 100.0 % All set-ups TRUE -1 Uint32
2-17 Over-voltage Control [2] Enabled All set-ups TRUE - Uint8
5.1.4. 2-** Brakes
VLT
®
HVAC Drive Programming Guide 5. Parameter Lists
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark