0-43 [Reset] Key on LCP
Option: Function:
[0] Disabled No function
[1]
*
Enabled [Reset] Key is enabled
[2] Password Avoid unauthorized resetting. If par. 0-43 is included in the My Personal Menu, then define the password in
par.
0-65, Personal Menu Password
. Otherwise define the password in
par. 0-60, Main Menu Password
.
3.2.7. 0-5* Copy / Save
Copy parameter settings between set-ups and to/from the LCP.
0-50 LCP Copy
Option: Function:
[0]
*
No copy No function
[1] All to LCP Copies all parameters in all set-ups from the frequency converter memory to the LCP memory. For service
purposes it is recommended to copy all parameters to the LCP after commissioning.
[2] All from LCP Copies all parameters in all set-ups from the LCP memory to the frequency converter memory.
[3] Size indep. from LCP Copies only the parameters that are independent of the motor size. The latter selection can be used to pro-
gramme several frequency converters with the same function without disturbing motor data which are already
set.
This parameter cannot be adjusted while the motor is running.
0-51 Set-up Copy
Option: Function:
[0]
*
No copy No function
[1] Copy to set-up 1 Copies all parameters in the present edit set-up (defined in par. 0-11
Programming Set-up
) to Set-up 1.
[2] Copy to set-up 2 Copies all parameters in the present edit set-up (defined in par. 0-11
Programming Set-up
) to Set-up 2.
[3] Copy to set-up 3 Copies all parameters in the present edit set-up (defined in par. 0-11
Programming Set-up
) to Set-up 3.
[4] Copy to set-up 4 Copies all parameters in the present edit set-up (defined in par. 0-11
Programming Set-up
) to Set-up 4.
[9] Copy to all Copies the parameters in the present set-up over to each of the set-ups 1 to 4.
3.2.8. 0-6* Password
Define password access to menus.
0-60 Main Menu Password
Option: Function:
[100]
*
-9999 - 9999 Define the password for access to the Main Menu via the [Main Menu] key. If par. 0-61
Access to Main Menu
w/o Password
is set to
Full access
[0], this parameter will be ignored.
0-61 Access to Main Menu w/o Password
Option: Function:
[0]
*
Full access Disables password defined in par. 0-60
Main Menu Password
.
[1] Read only Prevent unauthorized editing of Main Menu parameters.
[2] No access Prevent unauthorized viewing and editing of Main Menu parameters.
[3] Bus: Read only Read only functions for parameters on fieldbus and/ or FC standard bus.
[4] Bus: No access No access to parameters is allowed via fieldbus and/ or FC standard bus.
[5] All: Read only Read only function for parameters on LCP, fieldbus or FC standard bus.
VLT
®
HVAC Drive Programming Guide 3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
35
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals