6.5 Testing the Motor Operation
1. Press [Main Menu] twice on the LCP.
2. Press the navigation keys and the [OK] key to
navigate to parameter group 1-** Load and Motor
and press [OK].
3. Navigate to parameter 1-23 Motor Frequency and
enter the frequency from the motor nameplate.
4. Navigate to parameter 1-23 Motor Frequency and
enter the current from the motor nameplate.
5. Navigate to parameter 1-25 Motor Nominal Speed
and enter the speed from the motor nameplate.
6. Press [Status] to return to the operational display.
7. Press [Hand On].
8.
Press [
] to accelerate the motor.
9.
Press [
] to decelerate the motor.
10. Press [O].
Initial Start-up