[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
8-33 Parity / Stop Bits
Default value: [0] Even parity, 1 stop bit
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Parity and stop bits for the protocol using the FC port. For some of the protocols, not all options are available. Default value refers to
the FC protocol. Changing the protocol in parameter 8-30 Protocol may change the baud rate.
Table 190: Option:
[0]
Even parity, 1 stop bit
[1]
Odd parity, 1 stop bit
[2]
No parity, 1 stop bit
[3]
No parity, 2 stop bits
8-35 Minimum Response Delay
Default value: Configuration dependent
Parameter type: Range
2-setup: 1 setup
Conversion index: -3
Data type: u_int16
Change during operation: True
Specify the minimum delay time between receiving a request and transmitting a response. This is used for overcoming modem
turnaround delays.
Table 191: Range:
Min: 0.0010 s
Max: 0.5 s
Default value: Configuration dependent
8-36 Maximum Response Delay
Default value: Configuration dependent
Parameter type: Range
2-setup: 1 setup
Conversion index: -3
Data type: u_int16
Change during operation: True
Specify the maximum allowed delay time between receiving a request and transmitting the response. If this time is exceeded, no
response is returned.
Table 192: Range:
Min: 0.1 s
Max: 10.0 s
Default value: Configuration dependent
8-37 Maximum Inter-char delay
Default value: Configuration dependent
Parameter type: Range
2-setup: 1 setup
Conversion index: -3
Data type: u_int16
Change during operation: True
Specify the maximum delay time between 2 characters in a message. Exceeding this delay time causes the message to be discarded.
Table 193: Range:
Min: 0.005 s
Max: 0.025 s
Default value: Configuration dependent
4.9.3 8-4* FC MC Protocol Set
This parameter group is for PCD write and read configurations.
AU363928304090en-000101 / 130R0982106 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals