Table 201: Option:
[0]
Digital input
Activate the setup selection via a digital input.
[1]
Bus
Activate the setup selection via the serial communication port.
[2]
Logic AND
Activate the setup selection via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3]
Logic OR
Activate the setup selection via the serial communication port or via 1 of the digital inputs.
8-56 Preset Reference Select
Default value: [3] Logic OR
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
N O T I C E
This parameter is active only when parameter 8-01 Control Site is set to [0] Digital and control word.
Select control of the drive preset reference selection via the terminals (digital input) and/or via the bus.
Table 202: Option:
[0]
Digital input
Activate the preset reference selection via a digital input.
[1]
Bus
Activate the preset reference selection via the serial communication port.
[2]
Logic AND
Activate the preset reference selection via the fieldbus/serial communication port, and via 1 of the digital
inputs.
[3]
Logic OR
Activate the preset reference selection via the serial communication port or via 1 of the digital inputs.
4.9.5 8-7* BACnet
8-70 BACnet Device Instance
Default value: 1
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int32
Change during operation: True
Enter a unique ID number for the BACnet device.
Table 203: Range:
Min: 0
Max: 4194303
Default value: 1
8-72 MS/TP Max Masters
Default value: 127
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int8
Change during operation: True
Define the address of the master, which holds the highest address in this network. Decreasing this value optimizes polling for the
token.
Table 204: Range:
Min: 0
Max: 127
Default value: 127
8-73 MS/TP Max Info Frames
Default value: 1
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int16
Change during operation: True
AU363928304090en-000101 / 130R0982112 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals